TX7220 Addressable Dual I/O Module

  • EN54-18 Compliance
  • Built-in MCU processor and digital addressing
  • Two circuits 24VDC/2A Output relay contact and Conttrol module or two circuits Input Fire or Supervisory signal configuration
  • LED status indicator
  • Onsite Adjustable Parameter
  • Loop powered or external power supply
  • Surface mounting with fix base for simple installation
Get A Quote
Download Resources

Technical Specifications

Input Voltage 24VDC [16V to 28V]
External PSU: 20V to 28VDC
Current Consumption Loop Standby: 0.6mA, Alarm: 2.6mA
External PSU Standby: 0.6mA, Alarm: 45mA
Control Output Voltage 24VDC / 2A rating (per circuit)
Input Relay Normally Open dry contact
Input Resistance 5.1 Kohms / ¼ W (per circuit)
Protocol / Addressing T&A, Value range from 1 to 254
Indicator Status Normal: Single blink / Active: Steady / Fault: Double Blink
Material / Colour ABS / White Glossy finishing
Dimension (L×W×H) 108 × 86 × 38 mm
Weight 182g (with Base), 100g (without Base)
Operating Temperature -10°C to +50°C
Ingress Protection Rating IP30
Humidity 0 to 95% RH, Non-condensing