En
  • English

  • Japanese

  • Korean

TX7 Intelligent Fire Alarm System

TX7200 Addressable Input Module

  • EN54-18 Compliance
  • Built-in MCU processor and digital addressing
  • Fire or Supervisory signal configuration
  • Input cable monitored
  • Normally open configuration
  • LED status indicator
  • Loop powered device
  • Surface mounting with fix base for simple installation
Get A Quote
Download Resources

Technical Specifications

Input Voltage 24VDC [16V to 28V]
Current Consumption Standby: 0.7mA, Alarm: 1.2mA
Protocol / Addressing T&A, Value range from 1 to 254
Input Relay Normally Open dry contact
Input Resistance 5.1 Kohms / ¼ W
Indicator Status Normal: Single blink / Active: Steady / Fault: Double Blink
Material / Colour ABS / White Glossy finishing
Dimension (L×W×H) 108 × 86 × 38 mm
Weight 155g (with Base), 85g (without Base)
Operating Temperature -10°C to +50°C
Ingress Protection Rating IP30
Humidity 0 to 95% RH, Non-condensing